Model: CM-RI-01B/CM-RI-02B
Addressable Module
Product Features
- Two-wire communication
- Two types only: built-in input or inout/output relay can apply for all devices
- Stable communications, noise/interference resistant
- Monitoring loops of addressable module do not need voltage for connecting with conventional detectors
- Three-color LED indicator: monitoring, alarm, broken circuit
- Quick-install base design for improvement of installation efficiency
SPECIFICATIONS
MODEL NO. | RI-01B | RI-02B |
---|---|---|
FUNCTION | 1 input/1 output | 1 input |
RELAY OUTPUT | Control output both NO, NC connections Max. capacity: 2A/30V DC |
- |
POWER CONSUMPTION | 24V DC, max. 18mA in operation | |
COMMUNICATION LOOP | Fully two-wire multiplexing transmission, Internation resistance of communication cable < 12Ω, PE insulation wrapping of 500V communication cable > 2MΩ | |
SUPERVISE LOOP | 16V ~ 24V DC, max. output 1mA/24V DC sopplied by communication power; no extra power for relays; capable of receiving differential, heat, smoke, and other electronic detectors | |
TERMINAL | Addressable resistor | |
STATUS INDICATION | Monitoring: Green LED flashing Alarm: Red LED flashing Broken circuit: Orange LED flashing |
|
TEMPERATURE/RH | 0°C ~ 50°C, less 95% RH, non-condensing | |
DIMENSION | 35(W) × 80(H) × 35(D) mm | |
MATERIAL | Fire-proof plastics |